RCD trip-time limits (BS 7671)
The maximum operating time an RCD must meet on test, with the actual test currents for the device rating you pick. Compare them with the times on your tester.
Since Amendment 2 (2022) BS 7671 asks for one test: an AC test at the rated residual current IΔn, within 300 ms for a general RCD (130 to 500 ms for an S-type). Table 3A was deleted. The ×0.5 and ×5 lines are optional checks with the BS EN 61008 / 61009 limits, useful for fault finding.
What the RCD test is checking
An RCD has to disconnect fast enough to protect against electric shock. Since Amendment 2 (2022), BS 7671 asks for an alternating current test at the RCD's rated residual current (IΔn), whatever the RCD type, and sets the maximum operating time for that test. Your tester applies the current and times the trip. The figures above are the limits to compare against.
The required test and the optional ones
- x1 IΔn (required): a general (non-delayed) RCD must trip within 300 ms. An S-type is deliberately delayed (130 to 500 ms) so it can grade with RCDs downstream.
- x0.5 IΔn (optional): the RCD should not trip. Half the rated current should not be enough to operate it.
- x5 IΔn (optional): the fast test from the RCD product standards. A general RCD should trip within 40 ms.
30 mA and additional protection
Before Amendment 2, a 30 mA RCD providing additional protection also had to pass the ×5 test (150 mA) within 40 ms, using the times in Table 3A. That table was deleted in 2022 and the ×5 test is no longer required, though it is still a useful check when an RCD looks slow. Record the time from the ×1 test, and pair this with the max Zs checker for the disconnection side of fault protection.
FAQs
What is the maximum trip time for a 30mA RCD?
A 30 mA general (non-delayed) RCD must operate within 300 ms when tested at its rated current. Since Amendment 2 (2022) that is the only test BS 7671 asks for. The 40 ms limit at five times rated current (150 mA) comes from the RCD product standards and is now an optional check.
What should an RCD do at half its rated current?
It should not trip. At 0.5 times the rated residual current (15 mA for a 30 mA device) the RCD should hold, which shows it is not over-sensitive. BS 7671 no longer requires this test, but it is useful when you are fault finding.
What are the trip times for an S-type RCD?
An S-type (selective, time-delayed) RCD must trip between 130 and 500 ms at rated current. The optional test at five times rated current expects 50 to 150 ms. The delay lets it grade with non-delayed RCDs downstream.