Home › Templates › EICR template

EICR template and example

Looking for an EICR template? Here is exactly what an electrical installation condition report must contain, with an example of each section.

One caveat first: a valid EICR must be issued on the BS 7671 model forms by a competent person, with every circuit's results recorded and each observation coded, so a blank Word template is a study aid rather than a certificate you can hand a landlord. With that said, here is the full structure.

What an EICR must contain

EICR codes at a glance: C1, C2, C3 and FI

CodeMeaningEffect on the report
C1Danger present, risk of injury right nowUnsatisfactory. Make safe before leaving.
C2Potentially dangerousUnsatisfactory. Remedial work required.
C3Improvement recommendedReport can still be satisfactory.
FIFurther investigation requiredUnsatisfactory until investigated.

One C1, C2 or FI anywhere makes the whole report unsatisfactory. On a rented home those codes start a 28-day remedial clock for the landlord.

Worked EICR example: observations on a 1990s three-bed rental

Dummy data for a typical domestic report, showing how findings land in the observations section with a code and an action:

ObservationCodeAction
Socket outlet in the kitchen has a cracked frontplate with live parts touchableC1Replaced and made safe on the day
Downstairs socket circuit has no RCD protectionC2RCBOs quoted for the board
Main protective bonding to gas and water missingC210 mm² bonding quoted
Consumer unit pre-2016 in a combustible enclosure, no evidence of overheatingC3Improvement noted, no action required
Lighting circuit insulation reading could not be taken, joint box under loft insulation and inaccessibleFIFurther investigation booked
Overall assessmentUnsatisfactoryRemedial work within 28 days (rental)

For the wording behind each code and the borderline calls, see EICR codes explained, or check a specific observation with the EICR code checker.

Because the report is a legal document, it has to be on the model form with every test result recorded and each observation correctly coded. That is where a generic template falls down: SparkCerts produces the EICR to the BS 7671 model form, checks the readings as you type, and computes the overall verdict for you.

Common questions

Can I use a free EICR template?

A blank template is fine for learning the layout, but a valid EICR must be issued on the BS 7671 model forms by a competent person, with every circuit's test results recorded and each observation coded. SparkCerts produces the compliant report for you.

What is the difference between an EICR template and an example?

A template is the empty form; an example shows it completed. This page lists every section the report must contain, and our guides walk through what each one means.

Related: What is an EICR? · EICR codes explained · EICR software